3309 (Focus View) Series
3309 (Focus View) Specifications and Dimensions
Specifications
Parameter |
Value |
Linear Range |
2.0 mm (80 mils). Linear range begins at 0.38 mm (15 mils) from target and is from 0.38 to 2.41mm (15 to 95 mils). |
Incremental Scale Factor (ISF)
|
7.87 V/mm (200 mV/mil) +12.5%/–20% including interchangeability error when measured in increments of 0.25 mm (10 mils) over the 1.5 mm (60 mils) linear range |
Deviation from best fit straight line (DSL) |
Less than ±0.06 mm (± 2.3 mils) |
Frequency response |
0 to 10kHz (-3 dB) typical, with up to 100 meters (300 feet) of field wiring. |
Target Size |
Minimum: 8.9 mm (0.35 in) diameter Recommended minimum: 13mm (0.5 in) diameter Axial position measurements on shaft diameters smaller than 13mm (0.5 in) will generally result in a change in scale factor. Reducing the gap between the probe and target will help limit the change in scale factor. |
Shaft Diameter |
Minimum (standard X-Y probe configuration): 30 mm (1.2 in) Minimum (X-Y proximity probes offset axially by 23 mm (0.9 in)): 20 mm (0.8 in) Measurements on shaft diameters smaller than 30 mm (1.2 in) usually require close spacing of radial vibration or axial position transducers. This creates the potential for their electromagnetic emitted fields to interact with one another (cross-talk), resulting in erroneous readings. To prevent cross-talk, maintain minimum separation of m transducer tips of at least 25 mm (1.0 in) for axial position measurements or 23 mm (0.9 in) for radial vibration measurements |
Probe Tip Material |
Polyphenylene sulfide (PPS). |
Probe Cable Specifications |
75 Ω coaxial, fluoroethylene propylene (FEP) insulated probe cable in the following total probe lengths: 0.5, 1, 5, or 7 meters. |
Extension Cable Material |
75 Ω coaxial, fluoroethylene propylene (FEP) insulated. |
System Length |
5 or 7 meters including extension cable |
Extension Cable Armor (optional) |
Flexible AISI 302 SST with/without FEP outer jacket |
Tensile Strength (maximum rated) |
220 N (50 lb) probe case to probe lead. 220 N (50 lb) at probe lead to extension cable connectors. 220 N (50 lb) probe case to stainless steel armor |
Connector material |
Gold-plated brass |
Recommended Connector Torque |
Hand tightened |
Maximum torque |
0.56 N• m (5 in• lb) |
Minimum bend Radius (with or without SS armor) |
25.4 mm (1.0 in) |
Probe Temperature Range Operating Temperature |
-34°C to +177°C (-30°F to +351°F) |
Storage Temperature |
-51°C to +177°C (-60°F to +351°F) |
Extension Cable Operating and Storage Temperature |
-51°C to +177°C (-60°F to +351°F) |
Relative Humidity |
100% condensing, non-submersible when connectors are protected |
Imperial/US
Metric
Reverse Mount - Metric or Imperial
Extension Cables
3309 (Focus View) Ordering
Imperial/US
Model | A: Unthreaded Length | B: Overall Case Length | C: Total Length | D: Connector & Cable Type | E: Agency Approval |
MS330901 ¼-28 UNF thread, no armor |
Order in increments of 0.1 in |
Order in increments of 0.1 in |
05 = 0.5 Meter/20 in |
01 = Miniature coaxial connector, connector protector & standard cable |
00 = Not Required |
MS330902 ¼-28 UNF thread, with armor |
Example: 05 = 0.5 in | Example: 35 = 3.5 in |
10 = 1.0 meter/39 in |
02 = Miniature coaxial connector & standard cable |
05 = Multiple Approvals |
MS330908 ⅜-28 UNF thread, no armor |
Minimum unthreaded length: 0 mm | Minimum unthreaded length: 20 mm |
50 = 5.0 meter/16.4 feet |
11 = Miniature coaxial connector, connector protector & fluid block cable | |
MS330909 ⅜-24 UNF thread, with armor |
Maximum unthreaded length: 230 mm | Maximum unthreaded length: 250 mm |
70 = 7.0 meter/23.0 feet |
12 Miniature coaxial connector & fluid block cable |
Metric
Model | A: Unthreaded Length | B: Overall Case Length | C: Total Length | D: Connector & Cable Type | E: Agency Approval |
MS330903 M8 x 1 thread, no armor |
Order in increments of 10 mm | Order in increments of 10 mm |
05 = 0.5 Meter/20 in |
01 = Miniature coaxial connector, connector protector & standard cable |
00 = Not Required |
MS330904 M8 x 1 thread, with armor |
Example: 06 = 60 mm | Example: 06 = 60 mm |
10 = 1.0 meter/39 in |
02 = Miniature coaxial connector & standard cable |
05 = Multiple Approvals |
MS330905 M10 x 1 thread, no armor |
Minimum unthreaded length: 0 mm | Minimum unthreaded length: 20 mm |
50 = 5.0 meter/16.4 feet |
||
MS330910 M10 x 1 thread, with armor |
Maximum unthreaded length: 230 mm | Maximum unthreaded length: 250 mm |
90 = 9.0 meter/29.5 feet |
|
Reverse Mount
Option Descriptions
MS330906-02-12-CXX-DXX-EXX
MS330907-05-30-CXX-DXX-EXX
Model | AA: Total Length | BB: Connector & Cable Type | CC: Agency Approval |
MS330906-02-12 ⅜-24 UNF threads |
05 = 0.5 meter/20 in | 01 = Miniature coaxial connector, connector protector & standard cable | 00 = Not Required |
MS330907-05-30 M10 x 1 threads |
10 = 1.0 meter/39 in | 02 = Miniature coaxial connector & standard cable | 05 = Multiple Approvals |
50 = 5.0 meter/16.4 feet | |||
90 = 9.0 meter/29.5 feet |
Extension Cable
Extension Cable Option Descriptions
MS330930-AXXX-BXX-CXX
Model | AA: Cable Length | BB: Connector & Cable Type | CC: Agency Approval |
MS330930 |
040=4.0 meter/13.1 feet |
00 = No stainless steel armor. | 00 = Not Required |
045=4.5 meter/14.8 feet |
01 = Stainless steel armor & FEP Jacket. | 05 = Multiple Approvals | |
060=6.0 meter/19.7 feet |
02 = Stainless steel armor, no FEP Jacket | ||
065=6.5 meter/21.3 feet |
|||
080=8.0 meter/26.2 feet |
|||