Skip to main content

TriVibe Field Cable Options

We highly recommend using one of the cables that have been vetted by Machine Saver's Engineering Team, if you use a cable that is not specified on our list and have communication issues we may be unable to help you resolve them.

If you still wish to select another cable manufacturer, it is critical to get the following specifications correct:

Power pair of conductors: 18 AWG, twisted pair

Digital Modbus pair of conductors: 22 AWG, twisted pair

The cable capacitance should be low 12pF / foot

The cable impedance should be as close to 120 ohms as possible

There should be a foil shield 100% with a drain wire (overall or surrounding the digital Modbus pair)

 

  VTB-CBL-10 VTB-CBL-40 VTB-CBL-50
Cable Capacitance (pF/ft) 11 11 11

Impedance (Ohms)

120 120 105
Temperature Rating (°C) -80 to +200 -40 to +105 -20 to +80
Power Conductor Pair

18AWG
Red + Black
Twisted

No Power Pair Shield

18AWG
Red + Black
Twisted

100% Foil Shield

18AWG
Red + Black
Twisted

No Power Pair Shield

Weight (lbs/meter)

0.10

0.24

0.12

Data (Modbus) Conductor Pair

22AWG
Green + White
Twisted

No Data Pair Shield

22AWG
Green + White
Twisted

100% Foil Shield

22AWG
Blue + White
Twisted

100% Foil Shield

Drain 24AWG 24AWG 24AWG
Overall Shield 100% Foil Shield 100% Foil Shield No Overall Shield
Outer Jacket Material FEP (Red or Black) TPE (Black) PVC (Black)
Outer Jacket Thickness (in) 0.012 0.050 0.040
Outer Jacket Dimensions (in) 0.209 0.365 0.275
Bend Radius (in) 2.09 3.15 2.75
TriVibe Sensor Load (12) @ 1000 ft with a single power supply.

(22) @ 1500 -2000 ft with 2 Power Supplies and Sensor Distribution Dependent.
(12) @ 1000 ft with a single power supply.

(22) @ 1500 -2000 ft with 2 Power Supplies and Sensor Distribution Dependent.
(12) @ 1000 ft with a single power supply.

(22) @ 1500 -2000 ft with 2 Power Supplies and Sensor Distribution Dependent.
Certifications CL2, CMP UL and CSA Class I Div 2 UL444, NEC725 & 800
Suitability Sunlight Resistant, Direct Burial, Wet, Oil, Gas, Abraision, Acid, Indoor Sunlight Resistant, Direct Burial, Wet, Oil,  Abraision, High Stress Movement, Indoor, Outdoor Sunlight Resistant, Direct Burial, Indoor, Outdoor
Cycles N/A 5 Million N/A
Cost $$ $$$ $